Standby generators / 22 kW

22 kW standby generator: what it runs and what it burns

Generac's 22 kW Guardian is rated 22 kW on propane and 19.5 kW on natural gas. At full load it burns 3.9 gallons of propane an hour (2.53 at half load), so 100 gallons lasts about 25.6 hours at full load and 39.5 hours at half load.

Propane rating
22 kW
Natural gas rating
19.5 kW
Propane, full load
3.9 gal/h
Natural gas, full load
327 ft³/h
Refrigerator/freezer ×1: 700 WSump pump, 1/2 hp ×1: 1,050 WFurnace fan blower, 1/3 hp ×1: 700 WWell pump, 1/2 hp ×1: 1,000 WCPAP machine (ResMed AirSense 11) ×1: 73.2 WLED light bulb, 15 W ×6: 90 WCell phone charger ×2: 40 WTelevision, LED ×1: 80 WLaptop ×1: 60 WMicrowave, 1,000 W ×1: 1,000 WCoffee maker ×1: 1,500 WCentral air conditioner, 24,000 BTU (2 ton) ×1: 3,800 WElectric range, one 8-inch element ×1: 2,100 WWashing machine ×1: 1,150 WDishwasher ×1: 1,200 WRunning 14,543.2 W+ 4,950 W start = 19,493.2 Wnatural gas rating 19,500 Wpropane rating 22,000 W
A whole-home list the 22 kW carries on natural gas in this site's order, to scale; the cap is the biggest starting surge.

Generac's sizing page calls the 22 kW "the industry standard" for whole-home protection in 2,500 to 3,000 sq ft houses. It is rated 22 kW on propane and 19.5 kW on natural gas, a gap of 2.5 kW that is easy to miss when comparing quotes.

What it carries

Filling a whole-home list in a fixed order — essentials first (refrigerator, sump pump, furnace fan, well pump, CPAP, lights, electronics, microwave, coffee maker), then central air (2 ton), an electric water heater, a range element, washer, dishwasher, garage door and a desktop computer — and adding the single biggest starting surge to the running total as Generac's formula does, the 22 kW on natural gas carries 14,543.2 W running with a 4,950 W surge on top, 19.5 kW of its 19.5 kW. It has to leave out: Electric water heater, Garage door opener, 1/2 hp, Desktop computer with monitor. On propane it carries 16,693.2 W running, 21.6 kW with the surge.

Load (natural gas list)QtyRunning WExtra to start
Refrigerator/freezer17002,200
Sump pump, 1/2 hp11,0502,150
Furnace fan blower, 1/3 hp17001,400
Well pump, 1/2 hp11,0002,100
CPAP machine (ResMed AirSense 11)173.2—
LED light bulb, 15 W690—
Cell phone charger240—
Television, LED180—
Laptop160—
Microwave, 1,000 W11,000—
Coffee maker11,500—
Central air conditioner, 24,000 BTU (2 ton)13,8004,950
Electric range, one 8-inch element12,100—
Washing machine11,1502,300
Dishwasher11,2001,500

Central air with the basics alone needs 9.6 kW by the brochure figures — inside this unit's natural gas rating. Generac's sizing page warns that a 3-ton system "typically requires about 3.5kW to 5kW of running wattage" and can need 15 to 18 kW to start, far more than the brochure's 2-ton row; check the compressor's locked-rotor amps with an installer.

Fuel use

FuelHalf load, per hourFull load, per hourHalf load, per dayFull load, per day
Propane (gallons)2.533.960.793.6
Natural gas (cubic feet)2043274,8967,848
1.48103.07143.02183.74203.9223.9243.6326
Propane burned at full load, gallons per hour, for each Generac Guardian size (kW on the axis). From Generac's fuel table.

Half load burns 65% as much propane as full load, not 50%, so halving the load does not double the run time. Per-day figures assume the load holds steady for 24 hours; a real outage swings between the two. Generac's continuous-use guidance asks for a shutdown of at least 30 minutes after every 24 hours of running. The propane run-time guide works through a tank.

Fuel: Generac Support, How much fuel does my home standby generator use (Guardian Series table, Feb 12, 2026). Ratings: Generac Guardian 20/22/24 kW spec sheet.

Altitude and heat

Generac's spec sheet: "Maximum power decreases approximately 3.5% for each 1,000 ft (304.8 m) above sea level and approximately 1% for each 10 °F (6 °C) above 60 °F (16 °C)." At 5,000 feet that leaves 16.1 kW on natural gas and 18.2 kW on propane; on a 100 °F day at sea level, 18.7 kW and 21.1 kW. The calculator applies both when it picks a size, and the derating guide has a full table.

Smaller: 20 kW (18 kW on natural gas). Larger: 24 kW (21 kW on natural gas). Installation needs a transfer switch, a gas supply sized for full load, and the clearances in the installation manual.