What size generator runs a window air conditioner

Window air conditioner, 12,000 BTU: 3,250 W running plus 3,950 W more for a few seconds as it starts, so a generator needs at least 7,200 W of starting capacity to run it on its own. The smallest of the six portables this site covers that can do it is the Champion 201040 (7,500 W running, 9,375 W starting).

Running
3,250 W
Extra to start
3,950
Needed alone
7,200 W
With the basics
8,030 W
Honda EU2200ishortHonda EU3000iSshortWestinghouse iGen5000shortHonda EU7000iSshortChampion 201040fitsWestinghouse WGen9500DFfitsrun 3,250start 7,200 W
Window air conditioner, 12,000 BTU on its own needs 3,250 W running and 7,200 W to start. Bars: each generator's running rating (solid) and peak rating (track), to scale from zero.

The three tables disagree more on window air conditioners than on any other device. Generac and EWEB both list a 12,000 BTU unit at 3,250 W running and 3,950 W additional starting; Champion lists an unsized window unit at 1,200 W and 2,000 W.

Those are very different answers: the Generac figure needs about a 7,200 W starting capacity, the Champion figure about 3,200 W. The unit's nameplate (volts × amps, or watts) settles which applies to yours.

This page sizes from the Generac row, the cautious one, and shows the Champion row next to it.

The figures and where they come from

DeviceSourceRunning WAdditional starting WStarting need alone
Window air conditioner, 12,000 BTUGenerac GP brochure (2023)3,2503,9507,200
Window air conditioner, 12,000 BTUEWEB (2019)3,2503,9507,200
Window air conditioner, 12,000 BTU (Champion's row is an unsized window unit)Champion flyer (2021)1,2002,0003,200

Highlighted rows are the figures the calculator uses. Every table here prints additional starting watts: the surge on top of running watts.

Which portables can run it

GeneratorRunning / peak WAloneWith fridge, 6 LED bulbs, 2 chargers
Honda EU2200i1,800 / 2,200NoNo
Honda EU3000iS2,800 / 3,000NoNo
Westinghouse iGen50003,900 / 5,000NoNo
Honda EU7000iS5,500 / 7,000NoNo
Champion 2010407,500 / 9,375YesYes
Westinghouse WGen9500DF9,500 / 12,500YesYes

A generator fits when its running rating covers every running watt and its peak (or "max") rating covers the running total plus the single biggest starting surge. Adding the basics — a refrigerator (700 W running, 2,200 W to start), six 15 W LED bulbs and two phone chargers — raises the running load to 4,080 W and the starting need to 8,030 W. The smallest portable here that covers that is the Champion 201040.

Refrigerator/freezer ×1: 700 WLED light bulb, 15 W ×6: 90 WCell phone charger ×2: 40 WWindow air conditioner, 12,000 BTU ×1: 3,250 WRunning 4,080 W+ 3,950 W start = 8,030 WChampion 201040 running 7,500 Wpeak 9,375 W
Window air conditioner, 12,000 BTU with a refrigerator, six LED bulbs and two phone chargers, to scale. The orange-brown cap is the single biggest starting surge.

On a standby generator

A home standby unit is rated in kilowatts and has no overload capacity: Generac's rating definition says "No overload capability is available for this rating." Using Generac's own formula — sum of running watts plus the highest single starting burst — the window AC with the basics needs 8 kW. The smallest Guardian model that covers it on natural gas is the 10 kW, rated 9 kW on natural gas and 10 kW on propane, which leaves 1 kW of starting room for everything else. Whole-home lists are on the standby generator pages.

Before running anything, read the carbon monoxide distance rules and how a transfer switch keeps power off the utility lines. Other appliances: refrigerator · sump pump · well pump · furnace · central air · heat pump · space heater · water heater · washing machine · garage door opener · CPAP · oxygen concentrator.